Multi-Tube Hairpin Exchangers

A small tube bundle inside the hairpin for more surface

Contact us

Multi-Tube Hairpin Exchangers

Countercurrent Performance With Practical Surface Area

Put a small bundle of tubes inside the hairpin instead of a single pipe and you keep the countercurrent flow and the pressure capability while multiplying the surface. It is the natural step when a single-tube hairpin train would need too many sections.

The hairpin shell and the U-bend geometry stay the same. The result sits deliberately between a classic double pipe unit and a shell and tube exchanger, and it exists because there is a real gap between them.

The gap it fills. A single-tube hairpin runs out of surface quickly. A shell and tube gives plenty of surface but introduces baffles, which means crossflow, which means a correction factor on the temperature difference and the loss of a true temperature cross in one unit. A multi-tube hairpin gives several times the surface of a single-tube unit while keeping flow essentially countercurrent, because the shell-side fluid travels axially along the bundle rather than being forced across it.

The bundle comes out. Unlike a single-tube hairpin where the inner pipe is simply withdrawn, a multi-tube unit generally has a removable bundle with a proper tubesheet. The shell interior and the outside of the tubes can be inspected and cleaned, which extends the construction into fouling service that a sealed unit could not handle.

Condensing behavior. For condensing duty the multi-tube arrangement offers a useful choice that a single-tube hairpin does not. Condensing inside the tubes gives multiple parallel paths and good drainage in a vertical or sloped installation, with the coolant in the shell. Condensing on the shell side around the bundle gives a much larger flow area for the vapor, which is what you want when volumetric flow is high or pressure drop is constrained. That flexibility is one of the main reasons to step up from a single-tube unit.

bank of multi-tube hairpin exchanger sections stacked on a stainless support frame

Modularity survives. Multi-tube hairpins are still built in sections and manifolded, so surface can still be added later. The section count needed for a given duty is simply far lower, which keeps the connection count, support requirements and installed pressure drop manageable at duties where a single-tube train would have become unwieldy.

Related: single-tube hairpins for smaller duty, and shell and tube when the duty outgrows this construction.

Construction
Bundle in hairpin shell
Flow
Essentially countercurrent
Bundle
Removable, tubesheet
Tubes
Plain or finned

Configuration

  • Construction: Bundle in hairpin shell
  • Flow: Essentially countercurrent
  • Bundle: Removable, tubesheet
  • Tubes: Plain or finned

Features

  • Several times the surface
  • Removable tube bundle
  • Countercurrent retained
  • High pressure capable
  • Still modular in sections

Typical Condensing Duty

  • Mid-size vent condensing
  • Solvent recovery duty
  • Condensate subcooling
  • High pressure condensing
  • Fouling small duty
PRODUCT STYLE FLOW BUNDLE
Condenser / Cooler Multi-Tube Hairpin Countercurrent Removable

Choosing a Multi-Tube Hairpin

Which Side Should Condense

This is the useful decision that opens up once there is a bundle rather than a single tube. Condensing inside the tubes gives many small parallel paths, which drains well in a sloped or vertical installation and suits hygienic duty because the wetted side is smooth and cleanable. It works best when the vapor volumetric flow is moderate.

Condensing on the shell side around the bundle gives a much larger flow area, so vapor velocity and pressure drop stay low even at high volumetric flow. That is the arrangement for vacuum or near-vacuum duty and for any service where pressure drop is the binding constraint. The trade is that shell-side condensate drainage needs attention and the shell side is the harder side to keep hygienic.

Fins and the Weak Side

Longitudinal fins can be applied to the outside of the tubes in a multi-tube bundle just as they can on a single-tube hairpin, and the logic is the same: multiply area on whichever side has the poorer coefficient. In condensing service the condensing side usually has an excellent coefficient, so if fins help at all they help on the coolant side.

It is worth checking rather than assuming. A condensing stream heavily loaded with noncondensable gas can have a far poorer coefficient than clean condensing theory suggests, sometimes poor enough to become the controlling resistance. In that case fins on the coolant side buy nothing, and the honest answer is more area or a different configuration.

Knowing When to Move to Shell and Tube

Multi-tube hairpins extend the double pipe range considerably, but they do not extend it indefinitely. As duty grows, the number of sections climbs again and the same problems return: connection count, supports, accumulated pressure drop and installed cost. At that point a shell and tube exchanger with proper baffles will do the job in one shell for less money.

The signals that it is time to change are straightforward: more than a handful of sections, a temperature cross that is no longer required, or a duty where a single large shell would fit the plot comfortably. The signals to stay are equally clear: a genuine temperature cross, a pressure rating that would burden a shell, hazardous fluid where minimal inventory matters, or a real prospect of needing more capacity later.

Diagram: multi-tube hairpin heat exchanger with the tube bundle withdrawn from the shell

Multi-tube hairpin questions

The practical difference shows up in the thermal rating: the multi-tube hairpin uses the full log mean temperature difference with no correction factor. A baffled single-shell unit with two tube passes may lose 10 to 25 percent of that difference on a duty with a close approach, and on a condensing duty with subcooling that gap is often the difference between one unit and two.

The price of that is a lower shell-side coefficient, because fluid moving axially along a bundle is less turbulent than fluid forced across it by baffles. The multi-tube design makes it up with longitudinal fins where the shell-side fluid is a liquid or gas, and with length. Pressure is the other separation: the small-diameter hairpin shell carries high pressure as a pipe does, so a duty at 1,000 psi that would need a forged shell stays in hairpin construction comfortably.

Yes, the bundle slides out of the shell legs in to the clear space beyond the closure end, where the tubesheet sits, which means the installation needs a pull length equal to the section length plus working room. A 20 ft section therefore wants about 22 ft of clear aisle or a lifting path above it.

Plan for that before the pipe rack is laid out, because a multi-tube hairpin boxed in by piping becomes a sealed unit in practice. The tubes themselves are straight, so the bores can be brushed from the open end with the closure removed, and the outside of the bundle can be hydroblasted once it is out. For a condenser where the vapor side fouls with polymer or heavy ends, put the vapor into the tubes so the deposit lands on the surface that is easiest to reach.

Run the vapor volume first, because it settles the question before anything else does. Solvent vapor at 10 psig with a 6,000 lb/hr rate may occupy only a few hundred cubic feet per minute, which a bundle of 3/4 in tubes passes at a modest velocity with the coolant in the shell.

The same solvent at 2 psia occupies many times that volume, and forcing it into the tubes produces a pressure drop that eats the vacuum. That duty goes on the shell side, where the annular area around the bundle is several times the total tube bore area. Tube-side condensing also gives you a clean, drainable path that suits sanitary or hygienic service, while shell-side condensing needs a bottom outlet and a slight slope so condensate does not pool around the lower tubes.

Only when the coolant side is the larger resistance, and a quick two-number check tells you. Clean steam or solvent condensing on a tube can give a film coefficient above 1,000 Btu/hr sq ft F; a slow glycol or oil coolant may sit near 100, so fins on the coolant side are worth about five times the area and pay for themselves.

Bring 10 percent air into that vapor and the condensing coefficient can drop to a few hundred as the gas film builds at the wall; at that point the two sides are comparable and fins buy little. The failure we see is a finned unit specified from the clean coefficient for a stream that carries purge nitrogen or vacuum in-leakage, which then runs short on surface. If the inert fraction is uncertain, bare tubes with an extra section are the safer buy.

Count sections and count temperature cross, because those two numbers decide it. A multi-tube hairpin train that has grown past four to six sections carries the same connection, support and pressure-drop penalties that pushed you out of single-tube units, and a single shell will usually deliver that surface for less.

If the duty has a real temperature cross, though, the shell and tube needs two shells in series to match it, and the comparison changes back in favor of the hairpin. Weigh the plot as well: a 20 ft hairpin train runs along a rack, while a shell and tube of equal surface stands on its own saddles with a bundle pull space. For high pressure, minimal liquid inventory of a hazardous fluid, or a planned expansion, stay in hairpin construction past the point where cost alone would move you.

Several times more in the same length, which is what makes the step worthwhile. A single 2 in inner pipe in a 20 ft section gives roughly 25 sq ft of outside surface; put seven 3/4 in tubes inside a 4 in shell over the same length and the section carries about 55 sq ft, while a 6 in shell holding 19 tubes reaches roughly 150 sq ft.

The gain is in surface per section, not surface per dollar, so a multi-tube section costs more than a single-tube one and less than the three to six single-tube sections it replaces. For a 300 sq ft solvent recovery condenser that means two sections instead of twelve, with two closures, two sets of supports and a fraction of the field piping. The tube count also lets the vapor side be split across many parallel paths, which is the feature a single pipe cannot offer.

hairpin double pipe heat exchanger with a single inner tube and bolted end closures

Hairpin:

Single Inner Tube

  • Simplest construction
  • Very high pressure
  • Easy to clean
cutaway shell and tube exchanger showing the U-tube bundle, the next step up from a hairpin

U-Tube:

Next Step Up

  • Much larger duty
  • Removable bundle
  • Thermal shock rated
semi-welded plate heat exchanger with a gray frame, stainless plate pack and tie bolts, the compact option for aggressive duty

Welded Plate:

Compact Option

  • Very close approach
  • Small footprint
  • Clean duty only

Quote Request Form:

Questions?

1-805-484-2992

Quotes - Engineering - Sales